For sales and support visit:
hubbellpowersystems.com/contact/

Station Post Class Insulators

  • For outdoor use
  • Station Post Class Insulators
    Made from proprietary cycloaliphatic epoxy compounds
    with high mechanical and electrical properties
  • Non tracking material
  • Design based on ANSI C29.8 and C29.9 standards
  • Standard steel zinc plated inserts (copper or brass inserts
    available upon request)

Models

TR Post Insulators
Conforms to ANSI C29.8 and C29.9

Model BL Height
mm(in.)
Leakage
distance
mm(in.)
Number
of Sheds
Mounting
Pattern
Cantilever
Strength
kN (LBS)
Tensile Strength
kN (LBS)
Compression
Strength
kN (LBS)
Torsional
Strength
N-m in-(LBS)
Weight
kg (LBS)
T202A 95 191 (7.5) 428 (16.85) 5 3’’BC, 4x1/2-13 UNC 8.9 (2000) 31.1 (7000) 44.5 (10000) 678 (6000) 4.3 (9.5)
T205A 110 254 (10) 607 (23.90) 7 3’’BC, 4x1/2-13 UNC 8.9 (2000) 37.8 (8500) 44.5 (10000) 791 (7000) 5.3 (11.6)
T208A 150 356 (14) 943 (37.13) 11 3’’BC, 4x1/2-13 UNC 8.9 (2000) 44.5 (10000) 44.5 (10000) 904 (8000) 7.3 (15.9)
T210A 200 457 (18) 1232 (48.50) 15 3’’BC, 4x1/2-13 UNC 8.9 (2000) 53.4 (12000) 66.7 (15000) 1130 (10000) 9.8 (21.6)
T010A 200 381 (15) 965 (38.00) 11 3’’BC, 4x1/2-13 UNC 8.9 (2000) 31.1 (7000) 66.7 (15000) 1130 (10000) 7.9 (17.4)
T010P 180 381 (15) 769 (3 0.3) 9 3’’BC, 4x1/2-13 UNC
4 SLOTS BOTTOM
8.9 (2000) 31.1 )7000) 66.7 (15000) 1130 (10000) 7.7 (17.0)
Hubbell Power Systems All contents Copyright© 2001 - Hubbell Incorporated. All rights reserved. Because Hubbell has a policy of continuous product improvement, we reserve the right to change design specifications without notice.
Terms of Use | Contact Us | Site Map | Careers